We catch the right phase
| MOD5 | |
| Rated voltage: | 400, 415, 450, 525, 690 V |
| Frequency: | 50Hz |
| Capacitance tolerance: | -5... + 10% |
| Permissible continuous current: | 1,3In |
| Permissible short-time current (0,5 of period): | 200In |
| Maximum voltage -1.10Un -1.15Un -1.20Un -1.30Un |
8h/day 30min/day 5min/day 1min/day |
| Discharging devices: | Internal, discharge to 50V/1min. |
| Altitude: | <2000m a.s.l. |
| Work position | vertical |
| Ambient temperature: | -25...+ 55 C |
| Internal protection: | overpressure |
| Standards: | IEC60831 |