power factor correction

We catch the right phase

Capacitor switching contractors CQ type


CQ type contactors are designed for switching of capacitive circuits (capacitors) in three-phase low voltage networks of voltage up to 400V.
Technologies applied ensure reduction to minimum of transients (overvoltages, overloads) during switching of capacitive circuits. In case of single
capacitor switching by means of traditional capacitors, switching current can reach value 30 times higher than value of the capacitor’s rated current.
In case of capacitor bank with several grades, the value can exceed several hundred times the rated value. Such high currents might cause welding of
contactors’ contacts and damaging of capacitors. Construction of contactor with “smooth switching” circuits ensure switching transients limiting to
value permitted by IEC 60831 standard (≤100ICN by 0,5 of period).

General rated data

Type CQ12 CQ20 CQ32 CQ50
Rated voltage UN 400V
Insulation voltage Ui 660V
Control current 230V AC
Making ability for ambient temperature up to 40°C for voltage 400V [kVar] 12 20 32 50
Rated thermal currentIth [A] 26 43 69 108
Quantity of auxiliary contacts 1NO + 1NC 1NO + 1NC 1NO + 2NC 1NO + 2NC
Maximum quantity of operations
per hour
120
Electrical life (ambient temperature up to 40°C) 100000
Electrical life (ambient temperature up to 30°C) 300000
Mechanical life 1000000
Altitude ≤2000m. a.s.l.
Ambient temperature: -5...+40°C
Permissible power cables cross-section [mm2] 4 10 16 25
Permissible power cables cross-section [mm2] 1,5
Dimensions:
Drawing
A [mm]
B [mm]
C [mm]
D [mm]
E [mm]
F [mm]

1
max. 130
48
132
76
40
50/60

1
max. 130
58
137
86
40
50/60

2
max. 200
77
151
-
40
-

2
max. 200
87
160
-
40
-