We catch the right phase


Special executions foresee outdoor installation and operation in harsh environmental conditions (high temperature, humidity up to 100%, pollution, heavy dust).
Rated powers and voltages of capacitor banks AB-1Y and AB-2Y make series reactors (protective or in harmonics filtering system) connection possible. Reactors can be assembled on steel constructions or in separate cubicle with forced air cooling system.
General rated data:
| Frequency: | 50Hz (on request: 60Hz) |
| Temperature class: | -25/B -25°C...+45°C or -25/D -25°C...+55°C |
| Permissible voltages: | 1,10UN 12h/day 1,15UN 0,5h/day 1,20UN5 minutes 1,30UN 1 minute |
| Permissible transient overvoltages: | 2√2UN |
| Permissible continuous current: | 1,30IN |
| Permissible short-time overcurrent (0,5 of period) | 100IN |
| Active power losses (without reactors) | ≤0,15W/kVar |
| Discharging devices: | discharging to 50V within 5 minutes |
| Protection degree: | IP3X ... IP54 |
| Execution: | indoor or outdoor |
| Electric shock protection system: | earthing |
| Type: | AB-1 | AB-1Y | AB-2Y |
| Rated power: | 50...900kVar | 75...900kVar | 300...2400kVar |
| Rated voltage: | 3...11,5kV | 3...24kV | |
| Capacitors: | three-phase | single-phase | single-phase |
| Connection system: | delta | star | double-star |